National Institute for Land and Infrastructure Management (NILIM), Ministry of Land, Infrastructure and Building Research Institute (BRI), Transport and Tourism, National Research and Development Agency
4. Evaluation Method of Lighting Installations
This chapter shows the logic for calculating design primary energy consumptions of lightening installations.
4.1 Introduction
4.1.1 Scope of Application
The lighting installations that should be evaluated are defined below.
-
Lighting installation that is installed for indoor or outdoor use (limited to outdoor parking space, piloti or other similar space whose illuminated area is defined) in order to mainly ensure illumination that is necessary for any work or activity
-
Task lighting installation that is planned in combination with an ambient lighting instrument and whose layout, specs, etc. are described in drawings and specifications
-
Lighting installation that has a main role of distinct vision and also other roles (stairs/passage leading light etc.)
On the other hand, the following lighting installations are not evaluated.
-
Evacuation or lifesaving lighting system or other special-purpose lighting system (airplane warning light, heliport light, admission port red light, etc.)
-
Lighting installation to ensure safety (leading light, emergency lamp lighting only in case of emergency , etc.)
-
The lighting installation that is included in the lighting systems for ensuring distinct vision and shown below
-
Task lighting installation or other lighting instrument that is connected to an outlet and not described in drawings and specifications
-
Lightening system that has a high-level function or purpose (shadowless operating light, etc.)
-
Lighting system that does not light at all times and used for space with a short annual lighting time (equipment shaft etc.)
-
A lighting time in the case where the lighting system does not light at all times should be roughly based about 50 hours (about one hour a week) of annual lighting time.
-
-
Color lighting system to ensure stage management (exhibition lightening in showroom, lighting for stage management in stage, banquet hall or art museum, advertising light, etc.)
4.1.2 Definition of Terms
-
Lighting installation
This is an installation that is placed in combination with a light source, a lighting circuit and lighting fixtures with these components to form luminous environment. It is also called “lighting system.” When several different lighting fixtures are installed in one room, the same types of lighting fittings is interpreted as a group of lighting fittings. -
Lighting fixture
This has an optical function of controlling or adjusting a light emitted from a light source. In order to perform this function, it has a mechanical function of maintaining or protecting the light source and an electrical function of supplying or controlling electrical energy, -
Annual primary energy consumption of lighting installation
On the assumption that a lighting installation in all rooms to be evaluated in a building to be constructed is installed in a standard-shaped room (room index 2.5), this consumption is a hypothetical primary energy consumption that is calculated and expected to be consumed in a year. When a lighting control system is introduced, its energy reduction effect is reflected into the relevant primary energy consumption. Its unit is MJ/year. -
Basic unit for standard primary energy of lighting installation
On the assumption that a lighting installation with the most common lighting system and lighting fixtures of the moment is installed in a standard-shaped room (room index 2.5), this consumption is a hypothetical primary energy consumption per unit floor area (1㎡) that is expected to be consumed in a year. Its unit is MJ/m2/year. -
Power consumption of lighting fixture
This is a power consumption per one lighting fixture (including power consumed by a ballast when a lighting fixture requires the equipment). Its unit is W. -
Annual lighting time
This is an annual total value of lighting hours when a lighting fixture is expected to be lit in each room The effects of long and short lighting hours during actual operation of a lighting installation are avoided to objectively evaluate the installation. For this reason, the annual lighting time is a condition that is set for each room use on the basis of standard room use conditions as a common premise. -
Lighting control system
This is a system that automatically performs on-off control of lighting by one of various types of sensors, a timer or other similar device in order to cut (reduce) an energy consumption of a lighting installation. If the relevant control system is adopted, the effect of cutting the consumption is reflected into an annual primary energy consumption of the installation. -
Room index
This is a value that represents a relation between a frontage/depth and a light source height of a lighting installation. The larger this value is, the more luminous flux will directly reach a working plane from a light source. For this reason, its utilization factor (ratio of a luminous flux including an interreflected component that reaches the working plane to that emitted from the light source) becomes larger, and as a result, the luminous efficacy of the light source is improved.
4.1.3 Symbols and Units
Variable name | Description | Unit |
---|---|---|
\(RoomType_\{r}\) |
Building and room uses of room |
- |
\(H_\{r}\) |
Hight (Ceiling height) of lighting fixture in room |
m |
\(L_\{r}\) |
Size of frontage in room |
m |
\(D_\{r}\) |
Size of depth in room |
m |
\(K_{L,r}\) |
Room index of room r |
- |
\(E_{L,r,i}\) |
Power consumption of one lighting fixture i in room |
W/number |
\(n_{L,r,i}\) |
Number of installed lighting fixtures in room |
Number |
\(CtrlType_{LC1,r,i}\) |
Room detection and control method of lighting fixture in room |
Select |
\(CtrlType_{LC2,r,i}\) |
Brightness detection and control method for lighting fixture in room |
Select |
\(CtrlType_{LC3,r,i}\) |
Time schedule control method for lighting fixture in room |
Select |
\(CtrlType_{LC4,r,i}\) |
Initial illuminance correction method for lighting fixture in room |
Select |
\(N_\{room}\) |
Number of rooms to be illuminated in the whole of a building |
- |
\(N_{L,r}\) |
Number of types of lighting fixtures to be installed in room |
- |
\(C_{L,r}\) |
Coefficient determined according to the shape of room |
- |
\(F_{L,r,i}\) |
Coefficient determined according to control of or other method for lighting fixture in room |
- |
\(F_{LC1,r,i}\) |
Coefficient determined by room detection control method for lighting fixture in room |
- |
\(F_{LC2,r,i}\) |
Coefficient determined by brightness detection control method for lighting fixture in room |
- |
\(F_{LC3,r,i}\) |
Coefficient determined by time schedule control method for lighting fixture in room |
- |
\(F_{LC4,r,i}\) |
Coefficient determined by presence or absence of Initial illuminance correction function of lighting fixture in room |
- |
\(T_{L,r}\) |
Annual lighting time of lighting installation in room |
Time |
\(E_\{L}\) |
Primary energy consumption of lighting installation |
MJ/year |
4.1.4 Input/Output
The input/output in the whole of this chapter is shown in the following table.
Variable name | Description | Unit | Input sheet |
---|---|---|---|
\(RoomType_\{r}\) |
Building and room uses of room |
- |
Form 4 ① Building use, ① Room use |
\(H_\{r}\) |
Hight (Ceiling height) of lighting fixture in room |
m |
Form 4 ① Ceiling height |
\(L_\{r}\) |
Size of frontage in room |
m |
Form 4 ② Room frontage |
\(D_\{r}\) |
Size of depth in room |
m |
Form 4 ③ Room depth |
\(K_{L,r}\) |
Room index of room |
- |
Form 4 ④ Room index |
\(E_{L,r,i}\) |
Power consumption of one lighting fixture i in room |
W/number |
Form 4 ⑥ Rated power consumption |
\(n_{L,r,i}\) |
Number of installed lighting fixtures in room |
Number of fans j belonging to the air handling unit group |
Form 4 ⑦ Number |
\(CtrlType_{LC1,r,i}\) |
Room detection and control method of lighting fixture in room |
Select |
Form 4 ⑧ Room detection control |
\(CtrlType_{LC2,r,i}\) |
Brightness detection and control method for lighting fixture in room r |
Select |
Form 4 ⑨ Brightness detection control |
\(CtrlType_{LC3,r,i}\) |
Time schedule control method for lighting fixture in room |
Select |
Form 4 ⑩ Time schedule control |
\(CtrlType_{LC4,r,i}\) |
Initial illuminance correction method for lighting fixture in room |
Select |
Form 4 ⑪ Initial illuminance correction function |
\(N_\{room}\) |
Number of rooms to be illuminated in the whole of a building |
- |
- |
\(N_{L,r}\) |
Number of types of lighting fixtures to be installed in room |
- |
- |
Variable name | Description | Unit |
---|---|---|
\(E_\{L}\) |
Primary energy consumption of lighting installation |
MJ/year |
4.2 Coefficients Determined According to Control or Other Method
Calculate a coefficient determined according to control or other similar method stem: [F_{L,r,i}].
Variable name | Description | Unit | Reference |
---|---|---|---|
\(F_{LC1,r,i}\) |
Coefficient determined by room detection control method for lighting fixture in room |
- |
4.2.1 |
\(F_{LC2,r,i}\) |
Coefficient determined by brightness detection control method for lighting fixture in room |
- |
4.2.2 |
\(F_{LC3,r,i}\) |
Coefficient determined by time schedule control method for lighting fixture in room |
- |
4.2.3 |
\(F_{LC4,r,i}\) |
Coefficient determined by presence or absence of Initial illuminance correction function of lighting fixture in room |
- |
4.2.4 |
Variable name | Description | Unit | References |
---|---|---|---|
\(F_{L,r,i}\) |
Coefficient determined according to control of or other method for lighting fixture in room |
- |
4.5 |
Coefficients \(F_{LC1,r,i}\), \(F_{LC2,r,i}\), \(F_{LC3,r,i}\) and \(F_{LC4,r,i}\) are “Coefficient Determined by Room Detection Control Method (4.4.1),” “Coefficient Determined by Brightness Detection Control Method (4.4.2),” “Coefficient Determined by Time Schedule Control Method (4.4.3)” and “Coefficient Determined by Presence or Absence of Initial Illuminance Correction Function (4.4.4),” respectively. For each control, a value is specified according to its operation method.
in the case where substantial lighting consumption energy is reduced through introduction of each type of lighting control system, the coefficient determined according to each control method, \(F_{L,r,i}\), is equivalent to (1-Effect rate) at which the energy to be reduced is cut according to the effect of reducing the energy.
Controls or functions adopted for energy saving of lighting installations are classified into the following 4 categories from (a) to (d), thereby specifying a coefficient for each control or function method.
(a) Room detection control
(b) Brightness detection control
(c) Time schedule control
(d) Initial illuminance correction function
Only one operation method can be selected from the same categories for a lighting fixture to be installed in a room r (it is impossible to select several operation methods from the categories.). In the case where several lighting control systems with different categories are adopted to the same lighting fixture, a value multiplied by the coefficient of each category is assumed to be a coefficient for the fixture. However, a combination of operation methods that cannot be concurrently adopted due to a difference between applicable room uses or for other reason is excluded.
A lighting control system to which the coefficients can be applied should be only the same control system that can be expected to ensure to exert its effect and automatically controls illumination, and not include manual lighting control systems.
4.2.1 Coefficient Determined by Room Detection Control Method
Variable name | Description | Unit | Reference |
---|---|---|---|
\(CtrlType_{LC1,r,i}\) |
Room detection and control method of lighting fixture in room |
- |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(F_{LC1,r,i}\) |
Coefficient determined by room detection control method for lighting fixture in room |
- |
4.2 |
Room detection control refers to control under which a lighting fixture is turned on/off or dimmed based on a control signal etc. from a sensor etc. detecting the presence or absence of a person. A coefficient \(F_{LC1,r,i} \) , as shown in Table 8, is determined by a room detection control method to be adopted.
Option (operation method)/Direct input | Definition/Corresponding case | Coefficient \(F_{LC1,r,i}\) |
---|---|---|
Lower limit lighting control method |
Method in which a lighting fixture is automatically turned on/off based a signal from a human detecting sensor of continuous lighting control type |
0.95 |
Turning-on/off method |
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current with an automatic hot-wire switch |
0.70 |
Method in which a lighting fixture is automatically turned on/off based on a control signal from a human detecting sensor with on-off control |
||
Method in which a lighting fixture is automatically turned on/off based on a control signal from a built-in human detecting sensor with on-off control |
||
Dimming method |
Method in which a lighting fixture is automatically dimmed based on a control signal from a human detecting sensor with step control of lighting |
0.80 |
Method in which a lighting fixture is automatically dimmed based on a control signal from a built-in human detecting sensor with step control of lighting |
||
Absent |
Other method |
1.00 |
Direct input of the value |
Only when optional evaluation is allowed |
Input value |
If no operation method is specified (the relevant column on the input sheet is blank), "Absent" shall be assumed to have been selected.
The basis and judgment standard for setting a coefficient determined by the room detection control method are as shown in Annex C 2.
4.2.2 Coefficient Determined by Brightness Detection Control Method [changed in Ver. 2.4 and subsequent versions]
Variable name | Description | Unit | Reference |
---|---|---|---|
\(CtrlType_{LC2,r,i}\) |
Brightness detection and control method for lighting fixture in room |
- |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(F_{LC2,r,i}\) |
Coefficient determined by brightness detection control method for lighting fixture in room |
- |
4.2 |
Brightness detection control refers to control under which a lighting fixture is dimmed or turned on/off based on a comparison between an actual brightness level that includes daylight detected by a sensor etc., and a set brightness level brightness level. A coefficient \(F_{LC2,r,i}\), as shown in Table 11, is determined by a brightness detection control method to be adopted.
Option (operation method)/Direct input | Definition/Corresponding case | Coefficient \(F_{LC2,r,i}\) |
---|---|---|
Lighting control method |
Method in which a lighting fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control |
0.90 |
Lighting control method BL |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and automatic control blinds are concurrently used |
0.85 |
Lighting control method W15 |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control, and a room’s opening ratio of 15% or more |
0.85 |
Lighting control method W15BL |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and automatic control blinds are concurrently used, a room’s opening ratio of 15% or more, and automatic control blinds that are installed in 50% or more of its opening area |
0.78 |
Lighting control method W20 |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control, and a room’s opening ratio of 20% or more |
0.80 |
Lighting control method W20BL |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and automatic control blinds are concurrently used, and a room’s opening ratio is 20% or more, and automatic control blinds are installed in 50% or more of its opening area |
0.70 |
Lighting control method W25 |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and a room’s opening ratio of 25% or more |
0.75 |
Lighting control method W25BL |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and automatic control blinds are concurrently used, a room’s opening ratio is 25% or more, and automatic control blinds are installed in 50% or more of its opening area |
0.63 |
Turning-on/off method |
Method in which a lighting fixture is turned on/off based on a control signal from a brightness sensor with continuous lighting control |
0.80 |
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current through brightness detection of an automatic local switch |
||
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current through brightness detection of an automatic hot-wire switch (with a brightness sensor) |
||
Absent |
Other method |
1.0 |
Direct input of the value |
Only when optional evaluation is allowed |
Input value |
If no operation method is specified (the relevant column on the input sheet is blank), "Absent" shall be assumed to have been selected.
Where, an opening ratio is assumed to be a value obtained after the sum of window areas in a room are divided by a floor area of the whole room. In addition, an automatic control blind refers to a blind that automatically rotates the angles of slats or hoisting (lifting or lowering) the slats according to a solar position, an intensity of solar radiation or other element, and has the function of Grade B or higher in the Society of Heating, Air-conditioning and Sanitary Engineers of Japan SHASE-M1008-2009 “Planning manual of automatic blind system for environment-conscious buildings” (the function of automatically rotating the slats in the blind or lifting or lowering them by an electric motor and the system in which the function of judging a sunny or cloudy weather through measurement of outdoor illuminance, solar irradiance and other parameter is adjusted under a central control system).
The basis and judgment standard for setting a coefficient determined by a brightness detection control method are as shown in Annex C 3.
4.2.3 Coefficient Determined by Time Schedule Control Method
Variable name | Description | Unit | Reference |
---|---|---|---|
\(CtrlType_{LC3,r,i}\) |
Time schedule control method for lighting fixture in room |
- |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(F_{LC3,r,i}\) |
Coefficient determined by time schedule control method for lighting fixture in room |
- |
4.2 |
Time schedule control refers to control under which a lighting fixture is turned on/off or dimmed according to a preset time. A coefficient \(F_{LC3,r,i}\) is, as shown in Table 14, is determined by a brightness detection control method to be adopted.
Option (operation method)/Direct input | Corresponding case | Coefficient \(F_{LC3,r,i}\) |
---|---|---|
Dimming method |
Method in which a lighting fixture is dimmed according to a preset time |
0.95 |
Turning-on/off method |
Method in which a lighting fixture is dimmed according to a preset time |
0.90 |
Absent |
Other method |
1.0 |
Direct input of the value |
Only when optional evaluation is allowed |
Input value |
If no operation method is specified (the relevant column on the input sheet is blank), "Absent" shall be assumed to have been selected.
The basis and judgment standard for setting a coefficient determined by a time schedule control method are as shown in Annex C 4.
4.2.4 Coefficient Determined by Presence of Absence of I determined by the presence or absence of Initial Illuminance Correction Function
Variable name | Description | Unit | Reference |
---|---|---|---|
\(CtrlType_{LC4,r,i}\) |
Presence or absence of illuminance correction function of lighting fixture i in room |
- |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(F_{LC4,r,i}\) |
Coefficient determined by presence or absence of Initial illuminance correction function of lighting fixture in room |
- |
4.2 |
Initial illuminance correction control refers to the function of starting lighting with a luminous flux obtained after a rated flux is multiplied by a light loss factor. In order to implement the function, a timer built into a lighting fixture that memorizes a lighting time or a lighting control signal from a brightness sensor or other device shall be used. A coefficient, as shown in Table 17, is determined by the presence or absence of the function.
Option (operation method)/Direct input | Corresponding case | Coefficient \(F_{LC4,r,i}\) |
---|---|---|
Timer method (LED) |
Method in which a luminous flux is kept constant by a built-in timer for LED lighting fixtures |
0.95 |
Timer method (fluorescent lamp fixture) |
Method in which a luminous flux is kept constant by a built-in timer for fluorescent lamp fixtures |
0.85 |
Sensor method (LED) |
Method in which a luminous flux is kept constant by a brightness sensor for LED lighting fixtures |
0.95 |
Sensor method (fluorescent lamp fixture) |
Method in which a luminous flux is kept constant by a brightness sensor for fluorescent lamp fixtures |
0.85 |
Absent |
Other method |
1.0 |
Direct input of the value |
Only when optional evaluation is allowed |
Input value |
If no operation method is specified (the relevant column on the input sheet is blank), "Absent" shall be assumed to have been selected.
The basis and judgment standard for setting a coefficient determined by the presence or absence of the initial illuminance correction function are as shown in Annex C 5.
4.3 Coefficient Determined According to Room Shape
Determine a coefficient specified by a room shape, \(C_{L,r}\)[-] , using a room index \(K_{L,r}\)[-].
Variable name | Description | Unit | Reference |
---|---|---|---|
\(K_{L,r}\) |
Room index of room |
- |
Input |
\(L_\{r}\) |
Size of frontage in room |
m |
Input |
\(D_\{r}\) |
Size of depth in room |
m |
Input |
\(H_\{r}\) |
Ceiling height in room |
m |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(C_{L,r}\) |
Coefficient determined according to the shape of room |
- |
4.5 |
Use the inputted value of a room index \(K_{L,r}\). If a room index \(K_{L,r}\) is not inputted and \(L_\{r}\) and \(D_\{r}\) are inputted, determine the room index from the following formula.
Where, \(H_{L,r}\) is a height of a lighting fixture in a room r (difference between ceiling and working plane heights). For the working plane height, a proper value should be normally set, but for brevity, the height shall be uniformly a floor level of 0 m. Namely, the relevant height is assumed to be equal to be a ceiling height \(H_\{r}\) in a room r. In the case of \(H_\{r}\)=0, however, a coefficient \(K_{L,r}\)=2.5 shall be used.
A coefficient \(C_{L,r}\)[-] is specified in Table 20 based on the value of a room index \(K_{L,r}\)[-]
\(K_{L,r}\) | Less than 0.75 | 0.75 or more and less than 0.95 | 0.95 or more and less than 1.25 | 1.25 or more and less than 1.75 | 1.75 or more and less than 2.50 | 2.50 or more |
---|---|---|---|---|---|---|
\(C_{L,r}\) |
0.50 |
0.60 |
0.70 |
0.80 |
0.90 |
1.00 |
Where, in the case where all of the columns for frontage and depth sizes and ceiling height in the relevant room are blank, em:[C_{L,r}][-] is assumed to be 1.
The 2016 Building Energy Code prescribes a standard primary energy consumption, assuming that a room index in standard rooms is 2.5 and a reflection coefficient of ab interior finishing material is 50% for ceilings, 30% for walls and 10% for floors. However, correction is required to fill a gap between the standards and planned room specifications. The coefficient determined by a room shape plays the role of such correction. Where, considering that the reflection coefficient of the interior finishing material have a smaller effect on a utilization factor of the lighting fixture than the room index and that it is difficult to get information on an accurate reflection coefficient in an actual design, it was decided that only the room index would be corrected. A room with a small room index has a small utilization factor of the lighting fixture and tends to have a larger energy consumption per unit floor area. For this reason, in the case where a room index of a room has a smaller value than “2.5” assumed in calculation of a standard primary energy consumption, the room index is multiplied by a coefficient of less than 1 to discount a design primary energy consumption to be calculated.
4.4 Luminaire Lighting Time
Calculate \(T_{L,r}\), a luminaire lighting time
Variable name | Description | Unit | Reference |
---|---|---|---|
\(RoomType_\{r}\) |
Building and room uses of room |
- |
Input |
Variable name | Description | Unit | References |
---|---|---|---|
\(T_{L,r}\) |
Annual lighting time of lighting installation in room |
hours |
4.5 |
\(T_{L,r}\) is determined under the standard room use conditions according to building and room uses in a room r.
4.5 Power Consumption of Lighting Installation in Each Room
Calculate a power consumption of a lighting installation in each room, \(E_{L,r}\) [Wh/year].
Variable Name | Description | Unit | Reference |
---|---|---|---|
\(E_{L,r,i}\) |
Power consumption of one lighting fixture i in room |
W/number |
Input |
\(n_{L,r,i}\) |
Number of installed lighting fixtures in room |
Number of fans j belonging to the air handling unit group |
Input |
\(F_{L,r,i}\) |
Coefficient determined according to control of or other method for lighting fixture in room r |
- |
4.2 |
\(C_{L,r}\) |
Coefficient determined according to the shape of room |
- |
4.3 |
\(T_{L,r}\) |
Annual lighting time of lighting installation in room |
hours |
4.4 |
Variable Name | Description | Unit | References |
---|---|---|---|
\(E_{L,r}\) |
Power consumption of lighting installation in room |
Wh/year |
4.6 |
A power consumption of a lighting fixture, \(E_{L,r,i}\)[W], is a power consumption per one lighting fixture. A power consumption of a lighting fixture requiring a ballast is assumed to be a value that includes power consumed for this device.
If the power consumption of the lighting fixture is unknown at the time of application for evaluation, it is possible to determine its value in reference to the latest version of Guide 114 of Japan Luminaires Association (JLA).
In order to determine an annual operation time of a lighting installation, \(T_{L,r}\)[hour], use an annual luminaire lighting time under the following standard room use conditions. Namely, the conditions are determined according to building and room uses in a room r with the relevant lighting installation to be placed.
A coefficient determined by a control method for a lighting installation, \(F_{L,r,i}\)[-], is an energy reduction coefficient in the case where various types of automatic controls (only those automatically performed) are introduced to its lighting fixture. The method for calculating a coefficient \(F_{L,r,i}\) is specified in “4.3 Coefficient Determined According to Control or Other Method.”
A coefficient determined by a shape of a room r with a lighting installation to be installed, \(C_{L,r}\)[-], is a correction factor that is determined by a room index of a room to be illuminated. The method for calculating a coefficient \(C_{L,r}\) is specified in the following “4.3 Coefficient Determined According to room shape.”
4.6 Annual Primary Energy Consumption of Lighting Installation
Calculate an annual primary energy consumption, tem:[E_{L}] [MJ/year].
Variable Name | Description | Unit | Reference |
---|---|---|---|
\(E_{L,r}\) |
Power consumption of lighting installation in room |
Wh/year |
4.5 |
Variable Name | Description | Unit | References |
---|---|---|---|
\(E_\{L}\) |
Primary energy consumption of lighting installation |
MJ/year |
Output |
Annex C (Lighting)
C.1 Basis for setting a coefficient determined by room shape
In order to correct a gap between a standard room index and a utilization factor in a planned room index, a correlation between room indices and utilization factors for several types of lighting fixtures was examined. The result is shown in Table 4.5.1. A ratio of utilization factors (ratio between utilization factors of room index 2.5 and the relevant room index) depends on lighting fixtures, but for brevity, a correction factor that is determined by a room index was assumed to be uniform in all types of lighting fixtures.



C.2 Basis and judgment standards for setting a coefficient determined by room detection control method
Room detection control by a human detecting sensor or other device is an automatic control system that detects a person’s movement by an in-room human detecting sensor or other detector and turns lights on or off when the person is present or absent in a room, or dims the lights by lighting control, and whose effect depends on room uses or the size of the sensor’s on/off circuit. Local on/off or lighting control by a manual switch should not be evaluated. In addition, room detection control by a card or room key should not be evaluated either because it is used for the purpose of entry and exit control and accordingly, does not contribute to the effect of reducing a power consumption within business hours.
The definition of each control method and the basis for setting coefficient values are shown below.
1) Turning-on/off This is a control method in which a lighting installation is fully turned on if it is judged that an office worker etc. is present in a slightly wide range (a square of about 6.4 m that is equivalent to a standard span in an office building) of major space including an office in a building, but turned off if it is judged that the worker is absent there. Based on the data etc. on room detection in a turning-on/off range of a square of about 6.4 m in the survey on the project to promote the development or revision of building standards, an about almost 5% reduction is expected in the case where standard sensing is set at an occupancy rate of 50%. Accordingly, an energy reduction coefficient was assumed to be 0.95.
2) Turning-on/off (collectively turned-off) This is a control method for reducing energy consumptions in which lighting installations are fully turned on in a toilet, a warehouse, a corridor and other room where an office worker etc. stays for a short time if a human detecting sensor or other device judges that the worker is present there, but otherwise, they are collectively turned off. Based on the data etc. on the reduction rates by On-Off control in corridors and staircases in the survey on the project to promote the development or revision of building standards, an about 30% reduction is expected. Accordingly, an energy reduction coefficient was assumed to be 0.70.
3) Dimming method This is a control method for reducing energy consumptions in which a lighting installation is fully turned on in a corridor of a building or other space for office workers’ travel and without visual works if a human detecting sensor or other device judges that the workers are present there, but otherwise, they are dimmed by lighting control. Based on the data etc. on reduction rates by On-Off control in corridors and staircases in the survey on the project to promote the development or revision of building standards by the Ministry of Land, Infrastructure, Transport and Tourism (MLIT), an about 20% reduction is expected also in the case of dimming. Accordingly, an energy reduction coefficient was assumed to be 0.80.
Which method the relevant control belongs to shall be based on the conditions of hardware etc. shown in Table 27.
Control method | Conditions of hardware etc. | |||
---|---|---|---|---|
Name |
Definition |
Type of sensor etc. |
Type of lighting fixture |
Other condition |
Lower limit lighting control method |
Method in which a lighting fixture is automatically dimmed or turned on/off based on a signal from a human detecting sensor with continuous lighting control |
Human detecting sensor with continuous lighting control *Sensor etc. described as a standard drawing mark (:1) “AN” |
Continuous lighting control type ( lighting fixture that continuously controls an output and whose dimming lower value is 35% or less) |
- |
Turning-on/off method |
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current with an automatic hot-wire switch |
Automatic hot-wire switch *Wiring-based turning-on/off switch etc. described as a standard drawing mark (*1)“・RA” or “・RAS” |
Any type is accepted. |
A room to be illuminated should be a non-residential room (warehouse, toilet, corridor, etc.). |
Method in which a lighting fixture is automatically turned on/off based on a control signal from a human detecting sensor with on-off control |
Human detecting sensor with on-off control * Sensor etc. described as a standard drawing mark (*1) “N” |
|||
Method in which a lighting fixture is automatically turned on/off based on a control signal from a built-in human detecting sensor with on-off control |
Built-in human detecting sensor |
Built-in human detecting sensor (with on-off control ) *Defined as FDS1 for a fluorescent lamp fixture, and defined as LDS1 for a LED fixture in JIL (*2) |
||
Dimming method |
Method in which a lighting fixture is automatically dimmed based on a control signal from a human detecting sensor with step control of lighting |
Human detecting sensor with step control of lighting *Sensor etc. described as a standard drawing mark (*1) “NT” |
Continuous lighting control type ( lighting fixture that continuously controls an output and whose dimming lower value is 35% or less) |
|
Method in which a lighting fixture is automatically dimmed based on a control signal from a built-in human detecting sensor with step control of lighting |
Built-in human detecting sensor |
Built-in human detecting sensor (with on-off control ) |
*1: Marks described in the standard specification/drawing for electric insulation works (Electric power 63)
*2:JIL5004-2012
C.3 Basis and judgment standard for setting a coefficient determined by brightness detection control method
This is a lighting control system for reducing power consumptions in which dimming of a lighting installation is controlled automatically and finely in an area near to a side window with an incident daylight in a room with visual works and according to the brightness of the incident daylight. In order to detect the brightness of the daylight, a brightness detecting sensor is generally installed on the surface of a ceiling. The effect of controlling the brightness depends on a window orientation or position. In the case where an automatic control blind is installed, the blind makes the window’s luminance high, darkens the room relatively, and makes it possible to introduce a proper daylight without excessive illumination of the lighting installation. Accordingly, this increases the effect of interlocking control of the daylight. The use of daylight by a window installed at the upper part of a room, for instance, a roof light widow or high side light, is expected to be highly effective, but such a window requires a higher-level design than usual side windows, and the effect of energy reduction greatly depends on the conditions for installing the window. For these reasons, an energy reduction coefficient for the relevant window shall not be set in this manual.
The “On-Off method” is a control method in which space brightness such as daylight illuminance is detected by a sensor or other device, and a lighting installation is automatically turned off while a room maintains a certain level of brightness or higher and turned on when the room is darkened. This method helps to prevent forgetting turn on/off a lighting installation in areas without visual works, mainly such as a staircase, corridor and toilet.
The definition of each control method and the basis for setting coefficient values are shown below.
1) Lighting control method This is a lighting control system in which a lighting fixture near an one-way or continuous two-way window (unilateral daylighting) is dimmed in an office room of a building is dimmed according to an amount of incident daylight in the case where the window in the room is not automatically controlled by a blind. The control method was simulated, assuming the survey data in the project to promote the development or revision of building standards that are close to the above condition, an opening ratio of 10% or more, a perimeter ratio of 1/2 or more, and manual control of a blind. As a result, the rates of energy reduction produced by the one-way window and the continuous two-way window were about 10% or more. Consequently, an energy reduction coefficient was assumed to be 0.90.
2) Lighting control method (in combination with automatic control blind) This is a lighting control system in which a lighting fixture near an one-way or continuous two-way window (unilateral daylighting) is dimmed in an office room of a building is dimmed according to an amount of incident daylight in the case where the window in the room is automatically controlled by a blind. The control method was simulated, assuming the survey data in the project to promote the development or revision of building standards that are close to the above condition, an opening ratio of 10% or more, a perimeter ratio of 1/2 or more, and manual control of a blind. As a result, the rates of energy reduction produced by the one-way window and the continuous two-way window were about 15% or more. Consequently, an energy reduction coefficient was assumed to be 0.85.
3) On-Off method Given that this method has an energy reduction effect of 20% in the same way as the Evaluation Method for Calculating CEC/L under 2009 Building Energy Code, an energy reduction coefficient was assumed to be 0.80.
Which method the relevant control belongs to shall be based on the conditions of hardware etc. shown in Table 28.
Control method | Conditions of hardware etc. | |||
---|---|---|---|---|
Name |
Definition |
Type of sensor etc. |
Type of lighting fixture |
Other condition |
B1) Lighting control method |
Method in which a lighting fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control |
Brightness sensor with continuous lighting control |
Continuous lighting control type ( lighting fixture that continuously controls an output and whose dimming lower value is 35% or less) |
The room to be dimmed has an opening (opening ratio (*3) of 1/10 or more). |
B2) Lighting control method (in combination with automatic control blind) |
Method in which a lightening fixture is automatically dimmed based on a control signal from a brightness sensor with continuous lighting control and automatic control blinds are concurrently used |
The room to be dimmed has an opening (opening ratio (*3) of 1/10 or more) with an installed automatic control blind (*4). |
||
B3) On-Off method |
Method in which a lighting fixture is turned on/off based on a control signal from a brightness sensor with continuous lighting control |
・The room subject to on-off control has an opening |
||
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current through brightness detection of an automatic local switch |
Automatic local switch (EE switch) |
Any type is accepted. |
・The room subject to on-off control has an opening |
|
Method in which a lighting fixture is automatically turned on/off by passing/shutting off a circuit current through brightness detection of an automatic hot-wire switch (with a brightness sensor) |
Automatic hot-wire switch (with brightness sensor) |
*1: Marks described in the standard specification/drawing for electric insulation works (Electric power 63)
*2:JIL5004-2012
*3: Sum of opening areas (m2)/floor area (m2) of the room
*4: Blind that automatically controls the angles of slats according to a solar position, an intensity of solar radiation or other element
C.4 Basis and judgment standard for setting a coefficient determined by time schedule control method
This is a lighting control system that turns on/off or dims a lighting installation at a preset time, and also automatically turns on/off or dims the installation according to the required illuminance levels of the installation before the commencement of each day’s work, during lunch time, during overtime work and at other occasions.
The definition of each control method and the basis for setting coefficient values are shown below.
1) Dimming method This is a lighting control system that dims a lighting installation by lighting control at a preset time in the case where the required levels of the installation in a building depends on the hours before a store opens, while it opens opened and after it closes. Based on an about 10% reduction of the data etc.on reduction rates by turning-off in the survey on the project to promote the development or revision of building standards, an about 5% reduction is expected in the case of dimming. Accordingly, an energy reduction coefficient was assumed to be 0.95.
2) Turning-off method This is a lighting control system that turns off a lighting installation at a preset time in the case where the required illuminance levels of the installation depend on the hours before the commencement of each day’s work, during lunch time and during overtime work. Based on the data etc.on reduction rates by turning-off in the survey on the project to promote the development or revision of building standards, an about 10% reduction is expected. Accordingly, an energy reduction coefficient was assumed to be 0.90.
Which method the relevant control belongs to shall be based on the conditions of hardware etc. shown in Table 29.
Control method | Conditions of hardware etc. | |||
---|---|---|---|---|
Name |
Definition |
Type of sensor etc. |
Type of lighting fixture |
Other condition |
C1) Dimming method |
Method in which a lighting fixture is dimmed according to a preset time |
Lighting control panel that allows for schedule control |
Continuous lighting control type ( lighting fixture that continuously controls an output and whose dimming lower value is 35% or less) |
A lighting schedule that includes a lighting control rate in a room to be dimmed is specified. |
C2) Off-On method |
Method in which a lighting fixture is dimmed according to a preset time |
<Any type is accepted.> |
A lighting schedule for a room to be turned on/off is specified. |
*1: Marks described in the standard specification/drawing for electric insulation works (Electric power 63)
*2:JIL5004-2012
C.5 Basis and judgment standard for setting a coefficient determined by presence or absence of Initial illuminance correction function
This is a lighting control system that expects a light source’s luminous flux to be reduced by controlling a lighting fixture’s illumination hours with a brightness sensor/timer and inhibits excessive illuminance (corrects initial illuminance) immediately after a building’s completion, after replacement of its lamp or during the initial time after cleaning of the fixture in order to reduce power consumptions. Initial illuminance correction control is expressed as “proper illuminance control” in CEC/L under the 2009 Building Energy Code. When lighting installations were added to the scope of the Energy Conservation Act in 1993, the term of “initial illuminance correction control” was suggested, but it was judged that its formula would not adapt to legal terms, and as a result, the term of “proper illuminance control” was adopted. However, this Code employed the original term of “initial illuminance correction control” that indicates the content of the control more appropriately, in order to clarify a difference between the relevant term and the category (f) Illuminance lighting control by brightness sensor etc.
Based on the current curve for correction of initial illuminance that considers the lowering of an amount of its luminous flux due to aging of the fixture, an energy reduction coefficient for initial illuminance correction control was assumed to be 0.85, the same as the 2009 Code CEC/L. In order to determine an energy reduction coefficient for LED lighting fixtures, a maintenance rate for a lighting fixture designed based on the technical specifications of the Japan Luminaires Association (JLA), or 0.885 was conservatively rounded off to 0.90. On the assumption of the maintenance rate of 0.90, the relevant coefficient was calculated to be 0.95.
There are two methods for initial illuminance correction control that shall be evaluated; one (method using a brightness sensor) in which a brightness detection sensor is placed on the surface of a ceiling to detect a level of brightness on a working plane, thereby adjusting initial illuminance, and another in which the lighting fixture is preliminarily made to memorize data on a prediction curve for brightness decay, thereby changing its brightness by its timer according to lighting hours. The same energy reduction coefficient shall be applied to both of the two methods.
Which method the relevant control belongs to shall be based on the conditions of hardware etc. shown in Table 30.
Method | Conditions of hardware etc. | ||
---|---|---|---|
Name |
Definition |
Type of sensor etc. |
Type of lighting fixture |
D1) Timer method (LED) |
Method in which a luminous flux is kept constant by a built-in timer for LED lighting fixtures |
Built-in timer |
Initial illuminance correction type and LED lighting fixture |
D2) Timer method (Fluorescent lamp ) |
Method in which a luminous flux is kept constant by a built-in timer for fluorescent lamp fixtures |
Initial illuminance correction type and fluorescent lamp fixture |
|
D3) Sensor method (LED) |
Method in which a luminous flux is kept constant by a brightness sensor for LED lighting fixtures |
Brightness sensor with continuous lighting control |
Continuous lighting control type and LED lighting fixture (that continuously controls outputs by a lighting control signal and has a lighting control upper limit of 35% or less) |
D4) Sensor method (Fluorescent lamp) |
Method in which a luminous flux is kept constant by a brightness sensor for fluorescent lamp fixtures |
Continuous lighting control type and fluorescent lamp fixture (that continuously controls outputs by a lighting control signal and has a lighting control upper limit of 35% or less) |
*1: Marks described in the standard specification/drawing for electric insulation works (Electric power 63)
*2:JIL5004-2012